Special Application Waterflow Switch without Retard
The Model VS-SP is a vane type waterflow switch for use on wet sprinkler systems. These devices may be used as sectional flow indicators on large sprinkler systems and on smaller sprinkler systems such as mobile homes and residential dwellings.
The VS-SP does not have a retard to prevent false alarms due to water surges. Therefore it should NOT be used on systems with variable water pressure supplies except in the case of elevator recall.
New to DWG? - Sign Up for immediate access to dealer pricing and benefits.
Already a DWG Customer? - Sign In to view pricing.
These devices may be mounted in horizontal or vertical pipe. On horizontal pipe they should be installed on the top side of the pipe where they will be accessible. The units should not be installed within 6" (15cm) of a valve, drain or fitting which changes the direction of the water flow. Select the proper paddle for the pipe size and type of TEE used. See Fig. 1 for instructions on how to change the paddle. The unit has a 1" NPT bushing for threading into a non- corrosive TEE. See Fig. 2 for proper TEE size, type and installation. Use no more than three wraps of teflon tape as thread lubricant. Screw the device into the TEE fitting as shown in Fig. 2. Care must be taken to properly orient the device for the direction of waterflow.
The vane must not rub the inside of the TEE or bind in any way. The stem should move freely when operated by hand
Check the operation of the unit by opening the inspector’s test valve at the end of the sprinkler line, or the drain and test connection if a test valve is not provided.
If there are no provisions for testing the operation of the flow detection device on the system, application of the VS–SP is not recommended or advisable.
1111100 Specifications PDF