The cart is empty.
Your Trusted Partner for Expert Security Solutions.
DWG

FPO75-B100M8PNL4E4H LifeSafety Power Honeywell 4 Door 2 Amp 12VDC and 24VDC 8 Managed Class II Distribution Outputs Access Control Power Supply in UL Listed Indoor 20" W x 24" H x 6.5" D Electrical Enclosure

SKU: FPO75-B100M8PNL4E4H
  • 120 or 230 VAC input
  • 12 and 24 VDC outputs
  • On board Fire Alarm Interface
  • Continuous and resettable DC
  • Eight managed, power limited at 2.5A each
  • Eight managed - power limted at 2.5A each
  • Increased power, multiple voltages
  • Additional distribution outputs
  • Network monitoring and reporting
More details...
MPN: FPO75-B100M8PNL4E4H
Availability: Usually Ships within 2 to 3 Weeks
Ordering Notes: Service Professionals Only
MSRP Price: $1,263.00
Online Price: $843.00
Save to my Wish List

New to DWG? - Sign Up for immediate access to dealer pricing and benefits.

Already a DWG Customer? - Sign In to view pricing.



Product Details

HCLASS Unified Power Solutions are engineered to house FlexPower power modules alongside HW Pro-Watch access hardware in one compact, secure system. This unit is a 12V and 24V DC dual voltage network managed access power system.

M8P managed control module provide eight access control inputs capable of voltage or dry contact activation and eight Class 2 power limited outputs programmable for failsafe / failsecure operation at either 12 or 24 VDC and controlled by the integrated fire alarm interface circuit on the FPO.


Specifications


Input Power

  • Input 120/230 VAC 50/60 Hz | 83 Watts (0.70A)
  • Overload and short circuit protection
  • Over temperature protection
  • Polarized AC power supply disconnect

Output Power

  • 2A@12V and 2A@24V DC, 75W maximum combined output power
  • Outputs: Continuous (DC1) Resettable (DC2)
  • 8 managed outputs, class II power limited at 2.5A each
  • 120 mV output voltage ripple
  • System Efficiency: 83% | System BTU Rating: 33 BTU/Hr

Battery Charging

  • Independent built-in 1A charger for sealed lead acid or gel type batteries
  • Microprocessor dual rate charging of 12 or 24 V battery sets
  • Automatic switchover to standby battery when AC fails
  • Zero voltage drop when switched over to battery backup

Supervision

  • AC Fail (form "C" contacts)
  • System Fault (form "C" contacts) may be triggered by low/no battery, short to earth ground, power supply failure or blown fuse

Visual Indicators

  • AC input, DC1 and DC2 output
  • System fault | AC fault | Short to earth ground | Reverse battery polarity
  • Fire Alarm Input activated
  • B100: DC input, output and Fault
  • M8P: DC input, output and Fault

Regulatory Compliance

  • UL294, UL603, UL1076
  • ULC S318, ULC S319, CSA C22.2 #107.1, CSA 22.2 #60950
  • CE | CSFM Approved | FCC Part 15, Subpart B

Enclosure Dimensions

  • Size: 24.00H x 20.00W x 4.50D in. (61.00 x 51.00 x 11.50 cm)
  • Weight: 25 lbs.

Access Panel Mounting

  • Pro-Watch Controllers

FPO75-B100M8PNL4E4H Specifications PDF